VAMP Ltd
Feeder and motor manager
Technical description
VAMP 257
VM257.EN002
VAMP 24h support phone : +358 (0)20 753 3264
9
2.2.
Manager function dependencies
2.2.1.
Manager function reference guide
IEEE
no
IEC symbol
Function name
VA
MP 2
57
50/51
3I>, 3I>>,
3I>>
Overcurrent protection
X
67
I
dir
>, I
dir
>>,
I
dir
>>>,
I
dir
>>>>
Directional overcurrent protection
X
46 I
2
/I
1
>
Broken conductor protection
X
46 I
2
> Unbalance
protection
X
*
47
I
2
>>
Phase reversal / incorrect phase sequence
protection
X *
48 I
st
> Stall
protection
X
*
66
N>
Frequent start protection
X
*
37 I<
Undercurrent
protection
X
67N
Ι
0ϕ
>, Ι
0ϕ
>>
Directional earth fault protection
X
50N/51
N
I
0
>, I
0
>>, I
02
>,
I
02
>>
Earth fault protection
X
59N U
0
>, U
0
>>
Residual voltage protection
X
49 T>
Overload
protection
X
79
Auto reclose function
X
59
U>, U>>,
U>>>
Overvoltage protection
X
27
U<, U<<,
U<<<
Undervoltage protection
X
32
P<, P<<
Reverse and under power protection
X
81H/
81L
f><, f>><<
Over- and under-frequency protection
X
81L
f<, f<<
Underfrequency protection
X
81R
df/dt
Rate of change of frequency (ROCOF)
protection
X
68
2.ha
Second harmonic stage /inrush
X
50BF
CBFP
Circuit-breaker failure protection
X
50AR
ArcI>
Arc fault protection
X **
Fault
location
X
25
∆
f,
∆
U,
∆ϕ
Synchrocheck X
Protection
f
u
n
ction
s
Capacitor bank unbalance protection
X
3I Three-phase
current
X
l
0
Neutral
current
X
I
2
Current
unbalance
X
I
L
Average and maximum demand current
X
3U
Phase and line voltages
X
U
0
Residual
voltage
X
U
2
Voltage
unbalance
X
Xfault
Short-circuit fault reactance
X
Xfault Earth-fault
reactance
X
Measure
m
ent functions
f
System frequency
X
*) Only available when application mode is motor protection
**) Option