Appendix B: Regulatory information
100
ZP1-X3E Series Installation Manual
European standards
European standards for fire control and indicating equipment
These control panels have been designed in accordance with European
Standards EN 54-2, EN 54-4, and EN 12094-1.
In addition, all models comply with the following EN 54-2 and EN 12094-1
optional requirements.
Table 46: EN 54-2 optional requirements
Option
Description
7.8
Output to fire alarm devices [1]
7.9
Control of fire alarm routing equipment
7.9.1
Output to fire alarm routing equipment [2]
7.10
Output to fire protection equipment
7.11
Delays to outputs
7.12
Co-incidence detection, Type C only
8.3
Fault signals from points
8.4
Total loss of power supply
10
Test condition
[1] Inputs and outputs on the optional 2010-1-SB expansion board do
not
support the optional
requirement of EN 54-2 clause 7.8 and should not be used for fire alarm devices.
[2] Requires installation of optional 2010-1-SB expansion board (not supplied).
Table 47: EN 12094-1 optional requirements
Option
Description
4.17
Delay release of extinguishing agent
4.18
Indication of extinguishing agent flow
4.19
Monitor component status
4.20
Emergency hold device (mode A or B)
4.21
Control of flooding time
4.23
Manual mode
4.24
Trigger signals to equipment within the system
4.26
Trigger signals to equipment outside the system
4.27
Emergency abort device
4.30
Activate alarm devices with different signals