Chapter 2: Installation
ZP1-X3E Series Installation Manual
19
Figure 10: Connecting the batteries
Caution:
Risk of equipment damage. No other equipment may be connected to
the BATT connector.
Connecting other equipment
Connecting auxiliary equipment
Connect auxiliary equipment to the 24VAUX output as shown in Figure 11 below.
The 24 VDC auxiliary output is supervised for short circuit and voltage output.
Figure 11: Auxiliary power supply output connection (24VAUX)
1. External equipment to be powered with
24 VDC
See Table 28 on page 83 for the maximum current and other output ratings.
Caution:
Never use the auxiliary output to power expansion boards connected to
the same control panel as this might damage the control panel hardware.