Appendix A: Configuration presets
96
ZP1-X3E Series Installation Manual
Preset
ON status
Output
Delay
44
Extinguishing activation
1
Yes
2
Yes
Extinguishing released
3
Yes
4
Yes
46
Fire alarm
1
No
2
No
Activated
3
No
4
No
47
Pre-activated
1,2
No
Released
3,4
No
48
Hold on
1,2
No
Abort on
3,4
No
49
Manual mode
1,2
No
Automatic mode
3,4
No
50
Extinguishing disabled
1,2
No
Pressure switch fault
3,4
No
51
Door fault
1,2
No
Gas Flow on
3,4
No
52
Fire sounders [3]
1,2
No
Extinguishing sounders [3]
3,4
No
53
Optical panel [3]
1,2
No
Actuator [3]
3,4
No
55
Actuator blocked
1,2,3,4
No
80
Fire routing ON
1
No
2
No
3
No
4
No
90
Fire Sounders ON
1
No
2
No
Extinguishing sounders ON [4]
3
No
4
No
91
Fire Sounders ON
1
No
2
No
3
No
4
No