Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
53
A configured fire sounder delay may still be cancelled while the delay is running
(and sounders activated) by pressing the Fire Sounder Delay button.
Use this menu to configure the time while fire sounders silence is disabled. The
default setting is 1 minute.
To configure the Fire Sounders Silence Disabled Time:
1. Set the display as shown below, and then press Enter.
The Fire Sounders Start/Stop LED flashes fast to indicate that the Fire
Sounders Silence Disable Time configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Battery fault check
Use this menu to configure the battery fault check, on or off. This determines
whether the battery fault is supervised or not. The default setting is On.
Note:
If disabled, it does not comply with EN 54-2 and EN 54-4.
To configure the battery fault check:
1. Set the display as shown below, and then press Enter.
The power supply fault LED flashes fast to indicate that the battery fault check
menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your change
The available settings for this feature are shown below.
Display
Description
The battery fault check is enabled.
The battery fault check is disabled.