Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
69
The available settings for this feature are shown below.
Display
Description
The analogue remote node is added to the repeater
map.
The analogue remote node is not added to the repeater
map.
Firenet remote output control
Use this menu to configure an addressable compatible control panel in the fire
network to command the outputs of the conventional panel (fire sounders, fire
routing, and expansion board outputs) with advanced programming options.
Consult the addressable control panel documentation (including its configuration
utility software) if you require this type of advanced configuration.
If the control panel is configured for remote output control, it will no longer
activate outputs based on its own logic and will only activate outputs with
commands coming from the fire network.
This mode of operation is fail-safe (if the control panel detects a fire network
fault, the outputs will activate with the local logic or the remote commands).
By default, Firenet remote output control is off for standalone applications or
pure conventional fire networks where the control panel controls its outputs.
Firenet extinguishing global controls
Use this menu to configure extinguishing commands as local or global. By
default, this is Off (remote extinguishing commands are not accepted).
To configure the Firenet extinguishing global controls:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4). The Network fault
LED flashes fast to indicate that the Firenet menu is active.
3. Press Enter.
4. Save your changes.