Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
37
• The configured delay has been enabled
• The initiating device is a detector or a manual call point installed in an
automatic zone or the initiating device is a detector installed in a mixed zone
• The initiating device is in a zone configured for delays (the default
configuration)
If any of the above points are not true, then the control panel activates the fire
sounders and fire routing immediately after the detection of the fire alarm.
Sounder delays are bypassed when the alarm is detected in an extinguishing
zone.
Adding expansion boards
To add an expansion board to the system you must install the board and then
configure the system. See the expansion board’s installation guide for installation
instructions. See “Expansion board configuration” on page 60 for configuration
instructions.
Advanced configuration
The default password for advanced configuration is 4444. After entering the
password, the first displayed menu is the Advanced default configuration
(indicating advanced installer user level). For more information see “User level
passwords and indications” on page 27.
The advanced configuration menu
Configuration options for this menu are shown in the table below. More
information for each option is included in the related topic.
Table 15: The advanced configuration menu
Display
Menu
Values
Advanced default configuration
See Table 14 on page 32
EN 54-13 supervision
Of= EN54-13 supervision Off and class
B outputs
A= EN54-13 supervision On for zone
and class A expansion board outputs
Default: Off