CONTROL FUNCTION
OVERVIEW - SECTION B
BOILER / HIGH TEMP ZONES
The SYSTEMpro 311 can provide a reset supply water
temperature from the primary boiler loop to high temp mix
loops. Boiler zones piped into the primary loop will receive the
same water temperature as the current boiler supply
temperature. The boiler supply temperature is automatically
adjusted by the SYSTEMpro 311 based on the following
information you must enter into the control's Adjust Menu.
NOTE:
The SYSTEMpro 311 will automatically
calculate a reset ratio based on the data you input.
OUTDOOR DESIGN (OUT DSGN)
(See fig. a)
• The OUT DSGN is set to the outdoor design temperature
used on the heat-loss analysis for the project
BOILER DESIGN (Boil DSGN)
(See fig. b)
• The Boil DSGN temperature is the temperature the supply
water must be heated to heat the boiler zones when the
outdoor air is at the OUT DSGN temperature
BOILER MINIMUM (Boil MIN)
(See fig. c)
• The Boil MIN is the lowest water temperature that the control
is allowed to use as a boiler target temperature (Refer to the
boiler manufacturer’s literature)
• During mild conditions, if the control calculates a Boil TRG
temperature below the Boil MIN setting, the Boil TRG
temperature adjusts to at least the Boil MIN setting
NOTE:
During this condition, if the boiler is
operating near the Boil MIN setting, the Minimum
pointer turns on while the Boil TRG or Boil SUP
temperature is viewed
• If the installed boiler is designed for condensing operation,
set the Boil MIN adjustment to OFF
Section B1: General
60
CONTROL FUNCTION
OVER
VIEW
CONTROL FUNCTION OVERVIEW -
CONTROL FUNCTION OVERVIEW - Section B - Boiler / High Temp Zones
Boil MAX
Boil DSGN
OUT DSGN
WWSD
Boil ROOM
210
(99)
190
(88)
170
(77)
150
(66)
130
(54)
110
(43)
90
(32)
70
(21)
50
°
F
(10
°
C)
-20
(-29)
0
(-18)
20
(-7)
40
(5)
60
(16)
80
(27)
Outdoor Air Temperature
Su
pp
ly
W
a
ter T
e
m
p
eratur
e
Boiler Reset
Ratio
Boil MIN
Boil INDR
Adjust
o
F
a
Adjust
o
F
b
Adjust
o
F
c
Access Level
LTD
USER
INST
ADV
Access Level
LTD
USER
INST
ADV
Access Level
LTD
USER
INST
ADV
Summary of Contents for SYSTEMpro 311
Page 1: ...SYSTEMpro 311 Installation Manual...
Page 90: ...88 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 91: ...89 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 92: ...90 APPENDIX III APPENDIX III Application Drawings...
Page 93: ...91 APPENDIX III APPENDIX III Application Drawings...
Page 94: ...92 APPENDIX III APPENDIX III Application Drawings...
Page 95: ...93 APPENDIX III APPENDIX III Application Drawings...
Page 96: ...94 APPENDIX III APPENDIX III Application Drawings...
Page 97: ...95 APPENDIX III APPENDIX III Application Drawings...
Page 98: ...96 APPENDIX III APPENDIX III Application Drawings...
Page 99: ...97 APPENDIX III APPENDIX III Application Drawings...
Page 106: ......