OUTDOOR DESIGN (OUT DSGN)
(See fig. a)
1) Go to OUT DSGN item field in Adjust Menu
2) Set to the outdoor design temperature used in the heat-loss
calculation
RANGE: -60 to 50°F (-51 to 10°C)
DEFAULT: 10°F (-12°C)
BOILER ROOM (Boil ROOM)
(See fig. b)
1) Go to Boil ROOM item field in Adjust Menu
2) Set to the desired room temperature for the boiler/high
temp zones
RANGE: 35 to 100°F (2 to 38°C)
DEFAULT: 70°F (21°C)
NOTE: There is only a ±3°F (±1°C)
adjustment in the LTD Access Level.
BOILER INDOOR (Boil INDR)
(See fig. c)
1) Go to Boil INDR item field in Adjust Menu
2) Set to the room temperature used in original building heat-
loss calculations of the building
RANGE: 35 to 100°F (2 to 38°C)
DEFAULT: 70°F (21°C)
39
PROGRAMMING
PROGRAMMING - Step 1 - Programming the Control
Adjust
o
F
c
Access Level
LTD
USER
INST
ADV
Adjust
o
F
b
Access Level
LTD
USER
INST
ADV
Adjust
o
F
a
Access Level
LTD
USER
INST
ADV
Summary of Contents for SYSTEMpro 311
Page 1: ...SYSTEMpro 311 Installation Manual...
Page 90: ...88 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 91: ...89 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 92: ...90 APPENDIX III APPENDIX III Application Drawings...
Page 93: ...91 APPENDIX III APPENDIX III Application Drawings...
Page 94: ...92 APPENDIX III APPENDIX III Application Drawings...
Page 95: ...93 APPENDIX III APPENDIX III Application Drawings...
Page 96: ...94 APPENDIX III APPENDIX III Application Drawings...
Page 97: ...95 APPENDIX III APPENDIX III Application Drawings...
Page 98: ...96 APPENDIX III APPENDIX III Application Drawings...
Page 99: ...97 APPENDIX III APPENDIX III Application Drawings...
Page 106: ......