PROGRAMMING
PROGRAMMING - Step 1 - Programming the Control
Adjust
o
F
g
Access Level
LTD
USER
INST
ADV
WARM WEATHER SHUT DOWN (WWSD)
(See fig. g)
The control enters into WWSD when slab and outdoor
temperatures exceed MELTING temperature by more than
1.5°F (1°C).
1) Go to WWSD item field in the Adjust Menu
2) Set to an outdoor temperature at which the system no
longer needs to heat the zone to maintain a comfortable
temperature inside
RANGE: 35 to 100°F, OFF (2 to 38°C, OFF)
DEFAULT: 68°F (21°C)