MIXING MAXIMUM (MIX MAX)
(See fig. s)
1) Go to MIX MAX item field in Adjust Menu
2) Set to highest water temperature the control is allowed to
use as MIX TRG temperature
RANGE: 80 to 210°F, OFF (27 to 99°C, OFF)
DEFAULT: 180°F (82°C)
NOTE:
Do not exceed the water temperatures
shown for the following construction methods.
OUTDOOR DESIGN (OUT DSGN)
(See fig. t)
1) Go to OUT DSGN item field in Adjust Menu
2) Set to the outdoor design temperature used in the heat-loss
calculation
RANGE: -60 to 50°F (-51 to 10°C)
DEFAULT: 10°F (-12°C)
MIXING DEVICE SELECTION (MIXING)
(See fig. u)
1) Go to MIXING item field in Adjust Menu
2) Set the type of mixing device used (floating action mixing
valve “FLOT” or variable speed injection pump “VAR”)
RANGE: FLOT (Floating), VAR (Variable Speed)
DEFAULT: VAR
48
PROGRAMMING
PROGRAMMING - Step 1 - Programming the Control
Adjust
u
Access Level
LTD
USER
INST
ADV
Adjust
o
F
t
Access Level
LTD
USER
INST
ADV
• Concrete
150°F
• Poured Underlayment 140°F
• Radiant Wall/Ceiling
120°F
(using drywall)
• Joist No Plates
180°F
• Joist w/Plates
165°F
• Quik Trak
®
180°F
Adjust
o
F
s
Access Level
LTD
USER
INST
ADV
Summary of Contents for SYSTEMpro 311
Page 1: ...SYSTEMpro 311 Installation Manual...
Page 90: ...88 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 91: ...89 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 92: ...90 APPENDIX III APPENDIX III Application Drawings...
Page 93: ...91 APPENDIX III APPENDIX III Application Drawings...
Page 94: ...92 APPENDIX III APPENDIX III Application Drawings...
Page 95: ...93 APPENDIX III APPENDIX III Application Drawings...
Page 96: ...94 APPENDIX III APPENDIX III Application Drawings...
Page 97: ...95 APPENDIX III APPENDIX III Application Drawings...
Page 98: ...96 APPENDIX III APPENDIX III Application Drawings...
Page 99: ...97 APPENDIX III APPENDIX III Application Drawings...
Page 106: ......