Application:

This thermostat is a 120VAC Heating and Cooling Digital Temperature 
Control.  It is designed for use on 4-pipe and 2-pipe fan coil systems 
operating at 120VAC.  Switching of load circuits is through relay 
contacts, allowing the control to switch pilot duty and fan loads.  Fan 
cycles on/off automatically with calls for heating or cooling.  Two 
speed direct drive capability for fan motors up to 1/6 HP.  This 
thermostat operates from a single setpoint with automatic changeover 
from heating to cooling.  There is built in programming to alter the 
control characteristics to suit energy conservation needs.  

Installation Notice:

This high performance digital thermostat is designed to provide many 
years of superior comfort control when properly installed and maintained.  
To achieve maximum performance, this device is designed to draw 
room air into itself continuously.  Reasonable care must therefore be 
taken with regard to air quality at the time of installation as well as 
during periods of normal use, see operating conditions below.

Operating Conditions:

The electronic mechanisms incorporated within this unit REQUIRE 
operating conditions similar to other electronic devices intended for 
INDOOR USE ONLY, such as would be acceptable for TV and similar 
household appliances.  Relative humidity must be less than 95% and 
the atmosphere must be non-condensing.  For operation in bathrooms,
shower or pool areas, outdoor entryways, greenhouses and similar
applications, order HSK-4120U or NPK-4120U.  These products 
include protection for coastal/tropical applications, therefore they are 
suitable for use in high humidity environments. Air quality must be 
maintained FREE of heavy dust or debris which may infiltrate the 
interior of this device.  Installation in any space which is unfinished 
or undergoing repainting or general rehabilitation is also considered 
product abuse.  This device should be removed from service during 
any local construction activity.

Cleaning:

This device incorporates a high impact polycarbonate enclosure which 
is easily cleaned with a dry cloth or vacuum brush.  Occasional soiling 
may be cleaned with a soft cloth lightly dampened with water and/or 
mild cleaning solution.  IN NO CASE should this device be directly 
sprayed with or exposed to free flowing liquids, including water, which 
could penetrate its interior. 

FAILURE TO OBSERVE ANY OF THE ABOVE CONDITIONS OF USE 
WILL COMPLETELY VOID THE SUPPLIER WARRANTY.

 

                               

 

                                     CAUTION

MAKE SURE UNIT IS PROPERLY CONNECTED.  DAMAGE TO THE 
DIGITAL CONTROL CAN BE CAUSED BY MISWIRING, WHICH WILL 
VOID THE WARRANTY.  FOR SAFETY REASONS ALWAYS USE 
WIRE NUTS ON ALL WIRE CONNECTIONS!!!

User Note:  The top of this unit will become warm to the touch.  This is a 
normal operation.  Internal heating is employed to continuously convect 
air upward through the thermostat, thereby improving room air temperature 
measurement.  Direct conflict with a downward ceiling fan or system fan air 
flow may result in false temperature reading.  Locate thermostat to avoid 
interference.

Specifications:
Temperature Monitor Range: 

 32.0°F to 99.9°F (0.0°C to 37.7°C)

Setpoint Range:

  60.0°F to 85.0°F (15.5°C to 29.5°C)

*Setpoint Default: 

 72.0°F (22.0°C)

*Comfort Conditioning Limit Defaults:

  65.0°F (18.5°C) cooling

  

 

 

    

85.0°F 

(29.5°C) 

heating 

Display Format:

  Liquid Crystal Display (LCD)

Sampling Rate:

  Every 5 seconds

Accuracy:  

± 1°F (0.5°C)

Power Source: 

 120VAC

Load Rating:

  2 Amps heat/cool, 1/6 HP fan

*Fan Control:  Selectable:

  Auto cycle, Low, High  

 

Heat/Cool Control:  

1 heat and 1 cool circuit (2 Amps pilot duty)

*Default Temperature Extreme Prevention Limits:

  Maintains room temperature between 60.0°F and 85.0°F
  (15.5°C and 29.5°C) when thermostat is in economy mode

*Fan Purge Timer:

  30 seconds default

       

 

   

programmable 0 (off) to 180 seconds

Anti-short Cycle:

  3 minute hold in no call state at all times

*Cycle Rate:

  8 cycles per hour

*See Field Programming Instructions

Old thermostat

wire function

Power Feed

Neutral

Heat
Cool

Low Fan

Medium Fan

High Fan

Cable

wire color

HIGH

LOW

AUTO

ECONOMY

°F/°C

Decrease

Temperature

Switches between

°F and °C

Selects

Fan/Economy

Function

Increase

Temperature

4-Pipe Fan Coil Installation:

This device should be installed and serviced by a qualified technician.  
Junction box mounting is highly recommended.

1.     Caution:  

Make sure that power has been disconnected.

2.

  All wiring must comply with applicable codes and ordinances.

3.

  A thorough check-out of the system should be made after 

 

installation is complete.

4. 

If fan motor is larger than 1/6 HP and/or electric heaters are used 

  for heating, additional power relays will be required.

5. 

If retrofitting old thermostat, remove old thermostat from the 

  junction box, carefully noting the wire connections on the old unit.  
   Record wire color and terminal legends in spaces provided.

Disconnect old thermostat and remove any existing backplate or 
mounting plate.

Retrofitting with Existing Control Wiring:

Most 3 speed fan system's control wiring 
is sufficient to connect this 2 speed 
thermostat without adding a neutral wire.
This connection is achieved by using the 
third fan speed wire as a neutral.
Disconnect the unused fan speed wire 
from the fan motor and connect it to 
*Neutral.  Be sure to insulate the unused
fan motor wire to prevent shorts.  At the 
thermostat, connect the unused fan 
speed wire (now neutral) to the thermostat.

X

Unused Speed

Low Speed

High Speed

High Fan

(Yellow w/red str)

Low Fan

(Yellow)

Neutral (White)

*Neutral

Cut Wire

Cool (Blue)

Heat (Red)

Load Feed (Orange)

           Control Feed (Black)

Fan

Motor

Figure 1

Installation and Operating Instructions
HS/HSK-4120U
NP/NPK-4120U

Summary of Contents for HS-4120U

Page 1: ...ll become warm to the touch This is a normal operation Internal heating is employed to continuously convect air upward through the thermostat thereby improving room air temperature measurement Direct conflict with a downward ceiling fan or system fan air flow may result in false temperature reading Locate thermostat to avoid interference Specifications Temperature Monitor Range 32 0 F to 99 9 F 0 ...

Page 2: ...tic speed change ECONOMY fan function sequence with auto as the starting point Change Scale Units Slide the F C switch to the left to display F Slide the F C switch to the right to display C When the F C switch is invoked the thermostat will reset and display the default setpoint in the selected scale The default setpoint unprogrammed is 72 0 F or 22 0 C Cycle Timing Anti short cycle protection 3 ...

Page 3: ...lling for Cooling meter should read 120VAC from White to Blue When Cooling is deactivated meter should read 0VAC from White to Blue B When thermostat is calling for Heating meter should read 120VAC from White to Red When Heating is deactivated meter should read 0VAC from White to Red C When thermostat is calling for High fan meter should read 120VAC from White to Yellow w Red Stripe When High fan ...

Page 4: ...White and Black the voltage must be 120VAC To Check Continuity Using a Voltmeter with all loads connected Cooling supply pipe aquastat or season change switch to cool A When thermostat is calling for Cooling and Low Fan meter should read 120VAC from White to Orange and from White to Yellow When Cooling is deactivated meter should read 0VAC from White to Orange and from White to Yellow B When therm...