7.CONTROL SIGNAL (External I/O Connector)
101
7-5. External Output Signal
7-5-1. Pulse output 1
Data sent out to PULSE OUTPUT 1 depends on the settings in [FEED PULSE (W/P) 1] and
[PULSE WIDTH 1].
7-5-2. Pulse output 2
Data sent out to PULSE OUTPUT 2 depends on the settings in [FEED PULSE (W/P) 2] and
[PULSE WIDTH 2].
7-5-3. Upper limit (HI)
HI alarm turns ON (only while RUNNING) if the values of feed ratio [%] or load ratio
[%] exceeds the set value of Alarm Upper Limit [%]. Note that “COMPARISON OFF”
in [ALARM MODE] suppresses this alarm.
7-5-4. GO
GO output turns ON (only while RUNNING) if neither HI nor LO is activated. Note
that “COMPARISON OFF” in [ALARM MODE] suppresses this alarm.
7-5-5. Lower limit (LO)
LO alarm turn ON (only while RUNNING ) if the values of feed ratio [%] or load ratio
[%] become equal or less than the set value of Alarm Lower Limit [%]. Note that
“COMPARISON OFF” in [ALARM MODE] suppresses this alarm.
7-5-6. Weight error
This output turns ON (only while RUNNING ) if any one of the following output turns
on: LOAD, -LOAD, OFL1-5, or EXC
.
7-5-7. Belt moving
This output turns on (only while RUNNING) if belt speed has non-zero value.
7-5-8. Power ON
This output is ON while the system is powered.