3.DATA EXCHANGE WITH CPU
21
Complete
Simple comparison mode
Timing of Complete bit output is determined by the selection made in Weighing
function 2 (Complete signal output mode). Time duration for which this signal is
held “1” depends on the setting in complete signal output.
Sequence mode
Over/Under judgment enabled:
Criteria: Other than “Comparison OFF”, and non-zero Judging times have been
selected for Over/Under comparison.
Timing of Complete bit output is determined by the selection made in
Weighing function 2 (Complete signal output mode). Time duration for
which this signal is held “1” depends on the setting in complete signal
output.
Over/Under judgment disabled:
Criteria: Judging times is set to “0” (Over/Under judgment OFF)
Complete bit becomes “1” if SP3 goes low (OFF edge, 1
→
0) ignoring the
setting in the complete signal output mode (Weighing function 2).
Time duration for which this signal is held “1” depends on the setting in
complete signal output.
・
After an Complete signal output, Weight value must fall below
the 25% level of Final setting. Otherwise, Complete for next
run cannot change to “1”.
・
I f t h e v a l u e f o r F i n a l i s s e t t o “ 0 ” , C o m p l e t e m a y
spontaneously change to “1” when the F159 is powered.