3.DATA EXCHANGE WITH CPU
17
TARE OFF
ON edge (0
→
1) disables tare subtraction function. Set value for tare subtraction
remains intact.
DZ ON
ON edge (0
→
1) triggers Digital Zeroing (Gross weight is zero cleared).
Allowable range of digital zeroing is within the range set by DZ regulation
value. “Zero Error” occurs if the reading is out of this range.
※
Digital Zero is reset when turning off power.
DZ OFF
ON edge (0
→
1) disables Digital Zero function. “Zero Error” message will also
be cleared.
HOLD
While this bit is on “1”, Weight value and Comparison Value remain unchanged
(hold).
HOLD bit (13th bit of n+5 CH) remains high while HOLD is activated.
Digital tare subtraction
If “relay” is selected for tare subtraction trigger, this bit determines ON/OFF of
Digital tare subtraction function.
1: Digital tare subtraction is ON
0: Digital tare subtraction is OFF
Feed / Discharge
If “relay” is selected in Weighing mode setting, this bit determines ON/OFF of
Feed/Discharge switching.
1: Discharge control
0: Feed control
FF CPS.
If “relay” is selected in FF CPS. setting, this bit determines ON/OFF of FF CPS..
1: FF CPS. ON
0: FF CPS. OFF