3.DATA EXCHANGE WITH CPU
32
Weighing function 2
10
0
10
0
10
0
10
0
Sign convention for discharge control
1
:
Sign of Net weight not reversed
0
:
Sign of Net weight reversed
Completion signal output mode
2
:
Complete signal turns on when SP3 turns on, and
remains on until Compare time expires, or,
Complete signal turns on when reading becomes
“stable” and remains on until Complete output
time expires.
1
:
After Compare time expires, Complete signal
turns on when reading becomes “stable” and
remains on until Complete output time expires.
0
:
Complete signal turns on when Compare time
expires, and remains on until Complete output
time expires.
Upper/Lower limit comparison mode
1
:
Comparison when Judge input turns ON
0
:
Always
Over/Under comparison mode
3
:
Comparison when complete signal
turns ON. Weight will be frozen.
2
:
Comparison when complete output
turns ON.
1
:
Comparison when Judge input
turns ON
0
:
Always