Wireless Fire Alarm Control Panel VIT 01
Instruction manual
Page 38
Revision 10/02.17
Pages 51
-
еnter the zone (1-15).
Active buttons are:
buttons
and
- to select
the number of the zone (1-15);
button
- to return to the screen
for entering the name;
button
-
exit
to
menu
„Registration”.
Zone number uniquely determines the location of the detector. The available values of the parameter
are from 0 to 15. In values 1 to 15 the fire detector connects to the corresponding zone and upon
retransmiting information for fire condition, the Control Panel triggers the appropriate zone indications
and assigns the outputs specified in the its description.
At value 0 of the parameter, the fire detector does not connect to a specific zone. In this case upon
fire condition, the control panel produces only local sound signalization and a “Fire condition” signal
without activating additional outputs except mandatory output for activation - re
lay for “Fire”.
If the described device is a router, it shall be described by the procedure above, as only the name
requires description (the routers can be selected as addressable outputs for each zone).
Note: All fire detectors and manual call points are
assigned to Zone 1 with name “ZONE”
automatically. Fire detector’s name is predefined to “DETECTOR” , Router’s name to
“ROUTER” and Manulal call point ot “MAN. CALL”.
In case of fire in Zone 1, both monitored outputs
– OUT1 and OUT2 will be activated in Phase 2
without any additional settings from the engineering team!
12.4.3.3.3. Submenu
„Network Parameters”
Set up the following parameters:
Number (Address);
Time period of the connection;
Response time;
Parent.
Active buttons are:
-
buttons
and
- for changing the value of the selected parameter;
-
button
- to select a parameter;
-
button
- exit to menu
„Registration”.
Parameter
„Device Number”
The device number should be assigned in its
registration procedure. The numbers are from 1
to 32. The system should not have repeated
numbers and all duty is to the operator of the
system.