UniPOS
Wireless Fire Alarm Control Panel VIT 01
Instruction manual
Page 41
Revision 10/02.17
Pages 51
Parameter
„Measurement period in Duty
Mode”
The parameter sets the interval (in seconds) between
the two consecutive measurements of the device. It
defines the maximum respond time in case of a fire
condition or in case of fault in the devices.
This parameter has informative function for the
operator of the system and can not be changed.
Parameter
„Measurement period in Service
Mode
”
The parameter sets the interval (in seconds)
between the two consecutive measurements of the
device in Service Mode.
Parameter
„ Low Battery Level”
The parameter sets the level, under which, the
devices produce a fault signal "Low battery level".
Possible range 2.8V
– 3.5V. Default value – 3.0V.
Parameter
„Thermal sensor enabled”
The parameter is valid for VIT60.
This parameter allows for switching on or
switching off part of the combined fire detector.
Parameter
„Optical-smoke sensor
enabled
”
The parameter is valid for VIT60.
This parameter allows for switching on or
switching off part of the combined fire detector.