12.4.2.
Zones Set Up
The zone represents a number of fire detectors, grouped by a certain sign (usually the location)
For example:
Fire detectors on one floor in a building could belong to one zone
Setting a specific zone determines the way of reaction of the system in case of fire alarm in that
zone (which outputs of the Control Panel will be activated). The belonging of a detector to a zone
should be set in the parameters settings.
Zone description includes:
description of the parameters
– name, inspection time, time period between phases „Fire 1”
and
„Fire 2”, and button priority;
setting a list of outputs activated inphase
„Fire 1”;
setting a list of outputs activated in phase
„Fire 2”;
Upon entering menu "Zones", the display shows basic information about the first zone.
The first line displays the number and the
name of the zone. The second line displays the
number of the outputs in
„Fire 1” and „Fire 2”.The
last line shows the number of the fire detectors,
belonging to that zone.
Buttons
and
are displaying
information about the other zones in ascending
and in descending order.
Press button
to select the specific
zone for setting.
The submenu includes information about the
fire detectors, connected to the zone which is
under setting, the name of the zone, inspection
time and other parameters.
Press buttons
and
to make a
selection from the submenu.
12.4.2.1. „Check up fire detectors”
The screen shows the fire detectors,
connected to the zone one by one, providing the
following information:
line 1
– zone number and zone name;
line 3
– address and nameof FD;
line 4
– mode and status of FD;
Buttons
and
are displaying
information about the fire detectors, connected to
the zone in ascending and in descending order
Button
returns the display in menu
„Zones”.
12.4.2.2. „Parameters”
The submenu includes setting up of the following parameters of the zone:
Zone name;
Inspection time;
Time period between phases
„Fire 1” and „Fire 2” – default 60sec. 0-240sec.;
Manual Call Point Priority.