UniPOS
Wireless Fire Alarm Control Panel VIT 01
Instruction manual
Page 40
Revision 10/02.17
Pages 51
times (see LED indication) and after succesfull
operation,
the
operator
will
receive
an
acknowledgement for cleared parent with a fast
blinking of all LEDs followed by LED indication
corresponding to state “Connection” and
searching for new parent.
12.4.3.2.4. Submenu
„Measure parameters”
Set up the following parameters:
Class (for heat and combined fire detectors);
Sensitivity (for optical smoke and and combined fire detectors);
Measurement period in
„Duty Mode”;
Measurement period in “Service Mode”;
Level
„Low battery”;
Thermal sensor switched ON (for combined fire detectors);
Optical-smoke sensor switched ON (for combined fire detectors).
Active buttons are:
-
buttons
and
- to change the value of the selected parameter;
-
button
- to select parameter;
-
button
- exit to menu
„Registration”.
Parameter
„Class”
The parameter sets the class of the heat fire
detectors or the thermal part of the combined FD.
Admissible values are :
o
A1R;
o
A2R;
Parameter
„Sensitivity”
The parameter sets the sensitivity of the optical-
smoke detectors or the optical smoke sensor of
combined FD.
Possible values are:
o
Low ( 0.16db);
o
Middle (0.18db);
o
High (0.2db).