6.3. Using the keypad
The only one active button at that condition is
(“Menu”). The button is accessable for all the
Access Levels. Information about the status of devices, outputs, zones and Control Panel is available
at all access levels.
Note: In
„Duty Mode” the outputs of the Control Panel and the connected to it routers can be
forced to activate by pressing button
at access level 2 or higher. In this case the display shows
the text
„Evacuation”.
7. Fire condition
7.1. Description
The Fire Control Panel enters Fire condition mode upon activation of a fire detector of the system.
Exit from this mode is only through manual operation
– pressing button
with access level 2
or 3 password.
7.2. Indication
7.2.1.
LED and sound indication
In this condition are illuminated:
-
With green light indicator
(“Power supply”);
-
With red light indicator
(“Fire condition”);
-
With red light the indicator of the relevant zone
;
-
If the outputs for fire condition are suppressed by button
(“Outputs”), the LED
indicator of the button is illuminated in continuous red light;
-
If the sound indication is suppressed by button
(“Alarm”), the LED indicator of the
button is illuminated in continuous red light.
The local sounder produces a discontinuos signal
– fast beeping.
7.2.2.
Text indication
In this condition the display is divided into
two text fields:
On the first and on the second line it is
displayed information about:
-
Number of fire;
-
The fire detector in fire condition
(if it is only one);
-
The first fire detector, reported a
signal for fire condition (if there
are more than one signals for
fire)
On the 3
rd
and 4
th
line:
-
it is duplicated information about the fire detector in fire condition (of only one);
-
it is displayed information about the last activated fire (if more than one) and its
number.
The following information is visuslized on the display:
On the first line:
- Number of fire (
Example: 01
);
- The Phase of the Fire condition (
Example: Fire1
);
- Address and user description name of the fire detector (
Example: 17 Room
15
);
On the second line: