Revision 10/02.17
Pages 51
-
enter password for Access level 3.
The following features are accessible:
-
all accessable features of Access level 2;
-
entering and changing password for Access level 2 and level 3;
-
deleting the archive;
-
registration, exchange and exclusion of addressable points in the radio
network;
-
changing the parameters of the addressable points and zones.
5.1.4.
Access level 4
Accessible for personnel, trained and authorized by the producer to dismantle the fire control
panel and to modify the software. Special means are required for access this level.
5.2.
Means of control and indication
Wireless Fire Control Panel VIT01 operates in seven basic conditions: Duty Mode, Fire
condition mode, Fault condition mode, Disabled component mode, Test mode, Information and
control mode and Set Up mode.
At any moment, the control panel can be in one of them or in random combination of modes: Fire
condition, Fault condition, Disabled component, Test and Information and control.
The condition Set Up can not be combined with another condition.
Entering Set Up condition exits all the other conditions.
The Control Panel conditions and their corresponding indications are described in Table 1.
Table 1
Condition of the Fire Control Panel
Indication
All conditions -
The fire control panel is power supplied
Indicator Power supply
–
continuous green light
Fire condition Phase 1
– inspection time is entered
Indicator
„Time Delay” –
continuous yellow light (if time
delay is set)
Duty Mode, Fault condition, Information and control-
disabled components are available
Indicator
„Disabled component” –
in case of disabled component
Duty Mode, Fault condition, Disabled component,
Information and control
– Test Mode
Indicator Test
Fire condition
Common indicator
“Fire condition”
- red light in combination with the
individual indicator of the zone,
where the fire condition has been
registered.
Fault condition -
All fault conditions, excluding low power
Common indicator
“Fault
condition
” - continuous yellow light
Fault condition
– System fault
Indicator
“System fault” -
continuous yellow light
Fault condition
Indicator
“Fault in Power supply” -
continuous yellow light
Fault condition
Indicator
“Fault in a monitored
output
” - continuous yellow light
Fire condition
Local sounder- discontinuous signal
– fast
beeping