UniPOS
Wireless Fire Alarm Control Panel VIT 01
Instruction manual
Page 32
Revision 10/02.17
Pages 51
12.4.2.2.4. „Manual Call Point Priority”
The parameter determines if upon activation
the zone of a manual call point type VIT 50, the
panel will directly enter fire phase 2 mode for the
zone where the MCP belongs -
„Fire 2”.
Active buttons are:
buttons
and
- for
alternative change of the parameter
value
(„Yes” or „No”);
button
- for saving and
transition ;
button
-to exit in menu
„Zones”.
In this case
„inspection time” and „ time period phase1-phase2” are ignored.
Default value - Manual Call Point Priority is activated.
12.4.2.3. Submenu
„Output devices Ph1”
In this submenu set the outputs which will be
activated in condition
„Fire Ph1” of the zone.
The outputs within the system are shown
consecutively as parameters (Monitored output
1, Monitored output 2 and all outputs of the
registered routers (controllers). Each of them
must be set with value
„Yes” or „No”.
Thus there is a completed list of outputs that will
be activated in condition
„Fire Ph1”.
12.4.2.4. Submenu
„Output devices Ph2”
In this submenu set the outputs which will be
activated in fire condition mode
„Fire Ph2” of the
zone.
The outputs in the system are shown
consecutively as parameters (Monitored output
1, Monitored output 2 and all outputs of the
registered controllers). Each of them must be set
with value
„Yes” or „No
Thus there is a completed list of outputs that will
be activated in condition
„Fire Ph2”.
Active buttons are:
buttons
and
- for change
of the parameter value
(„Yes” or
„No”);
button
- for saving and
transition to next output in the list;
button
- to exit in menu
„Zones”.
12.4.3.
Menu
„Registration”
In the menu are available the following functions: