18
V. VENTING (continued)
Table 3: Vent Pipe Part Numbers
4" Direct Oil™ Vent Pipe
Pipe Length
Part No.
5 Ft.
8113302
10 Ft.
8113303
15 Ft.
8113304
20 Ft.
8113305
Figure 10: Intake Terminal Location
6. Intake Terminal Location (Direct Vent only) - Locate
Air Intake Terminal not less than 12 inches to the
left, right, or bottom of the vent terminal. Do not
locate air intake terminal above vent terminal.
Intake terminal must be at least 12 inches above
grade plus snow accumulation; at least 1 foot from a
roof soffit; at least 3 feet from an inside corner of an
L-shaped structure. See Figures 9 and 10.
7. The LEDV must be vented with 4" Z-Flex Direct
Oil™ Vent. 20 feet is the maximum vent length
allowed. The vent pipe is available in 5, 10, 15, and
20 foot lengths. Table 3 lists vent part numbers.
8. The vent system must be completed with the Direct
Oil™ Vent Kit, which is shipped with the boiler.
Components of this kit are listed in the Repair Parts
Section of this manual.
DANGER
Vent pipe may not be spliced. Do not drill through
vent pipe. Do not operate boiler if vent pipe has
been crushed. Vent pipe must be completely
sealed. Do not operate boiler if vent pipe
insulation sleeve is damaged, frayed or missing.
B.
Vent Installation
(Direct Vent and Side-Wall Vent)
1. Install Vent Terminal. See Figure 11.
a. After determining the location from previous
Section, cut an opening in the wall for the vent
terminal.
•
Combustible wall: 8 inches diameter hole is
required to maintain a 1 inch clearance to
combustible materials.
•
Non-combustible wall: 6½ inches diameter
hole is required.
b. Secure 10" square trim plate to outside wall.
c. Insert the vent terminal through the opening until
the stop bead rest against the trim plate.
d. Slide the 10" square inside trim plate assembly
(fitted with gear clamp) onto the terminal pipe.
Summary of Contents for LE DV Series
Page 5: ...5 I General Information Figure 1A LEDV Packaged Water Boiler with Beckett AFII Burner ...
Page 6: ...6 I General Information continued Figure 1B LEDV Packaged Water Boiler with Riello BF Burner ...
Page 19: ...19 v venting continued Figure 11 Vent Installation Figure 12 Vent Connector Un Assembled ...
Page 20: ...20 v venting continued Figure 13 Vent Connector Assembled Figure 14 Air Intake Installation ...
Page 48: ...48 xiii Repair Parts continued Figure 29 LEDV Bare Boiler Assembly ...
Page 50: ...50 xiii Repair Parts continued Figure 30 LEDV Boiler Jacket Insulation ...
Page 55: ...55 xiii Repair Parts continued Figure 33 Vent Kit Repair Parts ...
Page 60: ...60 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...