X. Operation
F. Changing Adjustable Parameters (continued)
2. Adjusting Parameters (continued)
The following pages describe the Control’s adjustable parameters. Parameters are presented in the order they appear on
the Control’s Display, from top to bottom and, left to right. From the “Home” screen select the Adjust button to access the
adjustment mode screens show below (if required, refer to the previous page to review how to enter Adjustment mode):
“Press”
System
Setup
button to access the following parameters:
Factory
Setting
range /
Choices
Parameter and Description
Fahrenheit
Fahrenheit,
Celsius
Temperature Units
The Temperature Units parameter determines whether temperature is represented in units of Fahrenheit
or Celsius degrees.
4
0-14
Display Brightness
Display brightness is adjustable from 0 to 14.
8
0-14
Display Contrast
Display contrast is adjustable from 0 to 14.
Wired
Not Installed,
Wired
Wireless
Outdoor Sensor Source
Not Installed Outdoor Sensor is not connected to the boiler, the sensor is not monitored for faults.
Wired Outdoor Sensor is installed and wired to boiler low voltage PCB.
Wireless Outdoor sensor is installed and wireless.
0
-50 to +50°F
tenths of degree
(-45.6 to 10°C)
Outdoor air Sensor Calibration
Outdoor Air Sensor Calibration offset allows a single point calibration. Using a reliable source (reference)
for outdoor temperature measure outdoor air temperature. Set the offset equal to the difference between
the controller reading and the reference. The result will be the Control’s measurement matching the
reference reading.
Not
Connected
Connected,
Not Connected
Zone Control Status Connected
When the Zone Control is connected adjustable settings are automatically shown under the Adjust
“Modulation”, “Auxiliary Heat” and “Zone Control Description Setup” menus. This feature allows these
adjustments to be made before the zone panel is connected. When the user selects “Show As If
Connected” Zone Control related parameters are made visible and may be adjusted.
Enabled
Enable/Disable
Frost Protection
Disable Frost Protection is not used.
Enable Boiler circulator starts and boiler fires when low outside air, supply and return
temperatures are sensed as follows:
0 min.
0-20 min.
anti-Short Cycle Time
Anti-short cycle is a tool that helps prevent excessive cy-cling resulting from a fast cycling Thermostat or
Zone valves. It provides a minimum delay time before the next burner cycle. DHW demand is serviced
immediately, without any delay.
Disabled
Enable/Disable
Warm Weather Shutdown Enable
Disable Warm Weather Shutdown (WWSD) is not used.
Enable The boiler and pumps will not be allowed to start in response to a central heat call for heat if
the outside temperature is greater than the WWSD setpoint. WWSD is initiated as soon as
outside air temperature is above WWSD Setpoint. The control does not require call for heat to
be satisfied.
The boiler will still start in response to a Domestic Hot Water call for heat.
70°F
(21.1°C)
20 to 100°F
(-6.7 to 37.8°C)
Warm Weather Shutdown Setpoint
The Warm Weather Shutdown (WWSD) Setpoint used to shutdown the boiler when enabled by the
“WWSD Enable” parameter.
Device
Started
Start
Temperatures
Stop
Temperatures
Boiler
Pump
Outside Air < -0°F (-18°C)
or Supply Water < 45°F (7.2°C)
Outside Air > -4°F (-16°C)
Supply Water > 50°F (10°C)
Boiler
Supply Water < 38°F (3.3°C)
Supply Water > 50°F (10°C)
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...