A. Installation of Factory Supplied Piping and
Trim Components
1. Install provided components
per Figure 25
for
ALP399C or Figure 26 for ALP500C through
ALP800C. Rear tapping is return/inlet. Front
tapping (middle on ALP399C) is supply/outlet.
Piping and trim components are located in
miscellaneous parts carton shipped with the
boiler.
a. Safety Relief Valve – Install on tee off 3/4 in.
NPT tapping on ALP399C or on tee off supply
tapping on ALP500C through ALP800C. Use
Vi. Water Piping and Trim
Figure 25: Factory Supplied Piping and Trim installation - aLP399C
nOTiCE
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
install boiler so that the gas ignition system components are protected from water (dripping, spraying,
rain, etc.) during appliance operation and service (circulator replacement, etc.).
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and
can lead to boiler failure. U.S. Boiler Company’ s Standard Warranty does not cover problems caused
by oxygen contamination of boiler water or scale (lime) build-up caused by frequent addition of water.
Do not fill boiler with softened water to prevent chloride contamination.
installation is not complete unless a safety relief valve is installed into the tapping located on left side
of appliance or the supply piping.
provided 10 in. long nipple to locate valve above
heat exchanger top.
b. Drain Valve – Install on tee off 3/4” NPT
tapping on ALP399C or on tee off supply tapping
on ALP500C through ALP800C.
c. Temperature and Pressure Gauge – Install on
supply piping.
d. Flow Switch – Install on supply piping. Use
provided tee with 1 in. NPT outlet. Use correct
paddle per Table 23. Refer to Section VIII
“Electrical” for flow switch wiring.
e. Install drain valve into tee bottom outlet.
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...