54
Warning
Explosion Hazard. Failure to properly pipe gas
supply to boiler may result in improper operation
and damage to the boiler or structure. always
assure gas piping is absolutely leak free and of
the proper size and type for the connected load.
an additional gas pressure regulator may be
needed. Consult gas supplier.
nOTiCE
Size corrugated stainless steel tubing (CSST)
to ensure proper capacity and minimize flow
restrictions.
A. Size gas piping. Design system to provide
adequate gas supply to boiler. Consider
these factors:
Inlet Pressure 14.0 in wc (3.4 kPa)or less; 0.3 in wc (0.07 kPa) Pressure Drop
Nominal Pipe
Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
131
90
72
62
55
50
46
42
40
38
¾
0.824
273
188
151
129
114
104
95
89
83
79
1
1.049
514
353
284
243
215
195
179
167
157
148
1¼
1.380
1060
726
583
499
442
400
368
343
322
304
1½
1.610
1580
1090
873
747
662
600
552
514
482
455
2
2.067
3050
2090
1680
1440
1280
1160
1060
989
928
877
2½
2.469
4860
3340
2680
2290
2030
1840
1690
1580
1480
1400
3
3.068
8580
5900
4740
4050
3590
3260
3000
2790
2610
2470
Table 29: Maximum Capacity of Schedule 40 Black Pipe in CFH* (natural gas) For gas Pressures
of 1/2 psi (3.4 kPa) or Less
* 1 CFH of Natural Gas is approximately equal to 1 MBH; contact your gas supplier for the actual heating value of your
gas.
1. Allowable pressure drop from point of
delivery to boiler.
Maximum allowable system
pressure is ½ psig (3.4 kPa). Actual point of delivery
pressure may be less; contact gas supplier for
additional information. Minimum gas valve inlet
pressure is printed on the rating label located in the
boiler’s vestibule compartment.
2. Maximum gas demand.
Refer to the boiler’s
input as printed on its rating label. Also consider
existing and expected future gas utilization
equipment (i.e. water heater, cooking equipment).
3. Length of piping and number of fittings.
Refer to Tables 29 (natural gas) or 30 (LP gas) for
maximum capacity of Schedule 40 pipe. Table 31
lists equivalent pipe length for standard fittings.
4. Specific gravity of gas.
Gas piping systems for
gas with a specific gravity of 0.60 can be sized
directly from Table 29 and gas with a specific
gravity of 1.5 can be sized from Table 30, unless
authority having jurisdiction specifies a gravity
factor be applied. For other specific gravity, apply
gravity factor from Table 32. If exact specific
gravity is not shown choose next higher value.
Vii. gas Piping
Inlet Pressure 14.0 in wc (3.4 kPa) or less; 0.5 in wc (0.12 kPa) Pressure Drop
Nominal Pipe
Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
172
118
95
81
72
65
60
56
52
50
¾
0.824
360
247
199
170
151
137
126
117
110
104
1
1.049
678
466
374
320
284
257
237
220
207
195
1¼
1.380
1390
957
768
657
583
528
486
452
424
400
1½
1.610
2090
1430
1150
985
873
791
728
677
635
600
2
2.067
4020
2760
2220
1900
1680
1520
1400
1300
1220
1160
2½
2.469
6400
4400
3530
3020
2680
2430
2230
2080
1950
1840
3
3.068
11300
7780
6250
5350
4740
4290
3950
3674
3450
3260
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...