17
iV. Venting
A. General Guidelines (continued)
Table 8: Vent and Combustion Air Pipe Sizes and Equivalent Lengths
(applies to all Listed Vent/Combustion air System Options)
Boiler
Model
Option
Combustion air Length
Vent Length
approx. Derate at
Max. Length
(%)
Pipe Dia., in.
(mm)
Min., ft.
(m)
Max., ft.
(m)
Pipe Dia., in.
(mm)
Min., ft.
(m)
Max., ft.
(m)
ALP399C
Standard
Diameter
4 (100 or 110)
0
100 (30.5)
4 (100 or 110)
2.5 (760)
100 (30.5)
5
Reduced
Diameter
3 (80)
0
50 (15.2)
3 (80)
2.5 (760 )
50 (15.2 )
5
ALP500C
Standard
Diameter
4 (100 or 110)
0
100 (30.5)
4 (100 or 110)
2.5 (760)
100 (30.5)
11
Reduced
Diameter
3 (80)
0
50 (15.2)
3 (80)
2.5 (760)
50 (15.2 )
12
ALP600C
Standard
Diameter
4 (100 or 110)
0
100 (30.5)
6 (150 or 160)
2.5 (760)
200 (30.5)
7
Reduced
Diameter
4 (100 or 110)
0
50 (15.2)
4 (100 or 110)
2.5 (760)
50 (15.2 )
10
ALP700C
Standard
Diameter
4 (100 or 110)
0
100 (30.5)
6 (150 or 160)
2.5 (760)
200 (30.5)
11
Reduced
Diameter
4 (100 or 110)
0
50 (15.2)
4 (100 or 110)
2.5 (760)
50 (15.2 )
15
ALP800C
Standard
Diameter
4 (100 or 110)
0
100 (30.5)
6 (150 or 160)
2.5 (760)
200 (30.5)
14
Reduced
Diameter
4 (100 or 110)
0
50 (15.2)
4 (100 or 110)
2.5 (760)
50 (15.2 )
15
Component
Equivalent Length
nominal Diameter
3 in. (80 mm)
4 in. (100 or 110 mm)
6 in. (150 or 160 mm)
90° Elbow, Short Radius
10 ft. (3.0 m)
13 ft. (4.0 m)
22 ft. (6.7 m)
90° Elbow, Long Sweep/Sanitary
4.0 ft. (1.2 m)
9 ft. (2.7 m)
17 ft. (5.2 m)
45° Elbow
3.0 ft. (0.9 m)
4.5 ft. (1.4 m)
7.5 ft. (2.3 m)
Table 9: Vent System and Combustion Air System Component Equivalent Length
(applies to all Listed Vent/Combustion air System Options)
Table 10: Vent and Combustion Air Equivalent Length Calculation Worksheet
Component
Combustion air
Vent
Equivalent
Length Per
Piece
x Quantity
=
Subtotal
Equivalent Length
Equivalent
Length Per
Piece
x
Quantity =
Subtotal Equivalent
Length
Straight Pipe
x
=
A
E
90° Elbow,
Short Radius
x
=
B
F
90° Elbow,
Long Sweep/
Sanitary
x
=
C
G
45° Elbow
x
=
D
H
Combustion air Total
Equivalent Length
=
a+B+C+D
Vent Total
Equivalent Length
=
E+F+g+H
Notes:
1. Total equivalent length cannot exceed maximum equivalent length shown in Table 8.
2. Use elbow equivalent lengths provided in Table 9.
3. Combustion air and vent terminations do not count towards total equivalent length.
4. Pressure drop for flexible polypropylene liner is 20% greater than for rigid pipe. Multiply measured flexible polypropylene liner
length by 1.2 to obtain equivalent length.
Example
Measured length = 35 ft.
Equivalent length =35 ft. x 1.2 = 42 ft.
5. Maximum equivalent length of flexible polypropylene liner is 48 ft. (14.6 m).
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...