78
iX. System Start-up
(continued)
Step
Parameter
Location
Parameter
Description
1
Adjust >>
System Setup
Outdoor Sensor Source
Select appropriate source: Not Installed, Wired or Wireless.
Warm Weather Shutdown
Enable/Disable
Selecting Enable will restrict boiler start during warm weather, but
only if an outdoor sensor is installed.
2
Adjust >>
Modulation Setup
Boiler Type
Warning
Confirm correct boiler model is shown. Stop installation and contact
factory if incorrect boiler model is shown.
3
Adjust >>
Pump Setup
Boiler Circulator
Ensure pump parameter selections are correct for your application.
System Circulator
Domestic Circulator
4
Adjust >>
Contractor Setup
Contractor Name
Enter contact information. In the event of a fault, or the need to
adjust a setting, the display will direct the user to the entered contact.
Contractor Address
Contractor Phone
5
Adjust >>
Central Heat
Setpoint
Ensure target space heating water temperature (Setpoint) is correct
for your type of radiation.
6
Adjust >>
Domestic Hot Water
Setpoint
Ensure target domestic hot water temperature (Setpoint) is correct.
DHW Modulation Sensor If using DHW Sensor, select DHW Sensor.
7
Adjust >>
Outdoor Reset
Central Heat
Enable/Disable
If not using an outdoor sensor, select Disable.
8
Adjust >>
Sequencer Master
Sequencer Master
If boiler is the master boiler in a multiple boiler installation, select
Enable.
9
Adjust >>
Sequencer Slave
Boiler Address
If boiler is a slave boiler in a multiple boiler installation, assign a
unique boiler address.
10
Adjust >>
Energy Management
Demand Source
If boiler is connected to an energy management system, and demand
will be through Modbus terminals, select Modbus.
nOTE:
Disable boiler internal sequencer when connecting to an
energy management system.
11
Adjust >>
Energy Management
Central Heat
Modulation Source
If using an external multiple boiler controller, set to 4-20 mA.
Central Heat Boiler
Setpoint Source
If an Energy Management System is sending a remote setpoint to the
boiler, set to 4-20 mA.
Table 41: Control Parameter Checklist
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...