113
Follow manufacturer application procedure
for proper heating system/boiler cleaning and
preventive treatment.
Above referenced products are available from
Alent plc, Consumer Products Division, 4100
6th Avenue, Altoona, PA 16602, Tel: (972)
547-6002 and/or selected HVAC distributors.
Contact U.S. Boiler Company for specific
details.
iii.
Sentinel
®
X400 System Restorer (For Older
Closed Loop Hydronic Heating Systems)
iv.
Sentinel
®
X300 System Cleaner (For New
Heating Systems)
v.
Sentinel
®
X100 Inhibitor (For Protecting
Closed Loop Hydronic Heating Systems
Against Lime scale And Corrosion)
Follow manufacturer application procedure
for proper heating system/boiler cleaning and
preventive treatment.
Above referenced products are available from
Douglas Products and Packaging, 1550 E. Old
210 Highway, Liberty, MO 64068, Tel:(877)
567-2560 (Toll Free) and/or selected HVAC
distributors.
2. System Freeze Protection:
a. The following heating system freeze protection
products are recommended for Alpine boilers:
i.
Fernox™ Protector Alphi 11 (combined
antifreeze and inhibitor).
Follow manufacturer application procedure
to insure proper antifreeze concentration and
inhibitor level.
Above referenced product is available from
Alent plc, Consumer Products Division, 4100
6th Avenue, Altoona, PA 16602, Tel: (972)
547-6002 and/or selected HVAC distributors.
Contact U.S. Boiler Company for specific
details.
ii.
Sentinel
®
X500 Inhibited Antifreeze
(combined antifreeze and inhibitor)
Follow manufacturer application procedure
to insure proper antifreeze concentration and
inhibitor level.
Above referenced products are available from
Douglas Products and Packaging, 1550 E. Old
210 Highway, Liberty, MO 64068, Tel:(877)
567-2560 (Toll Free) and/or selected HVAC
distributors.
b. Equivalent system freeze protection products
may be used in lieu of product referenced above.
In general, freeze protection for new or existing
systems must use specially formulated glycol,
which contains inhibitors, preventing the glycol
from attacking the metallic system components.
Insure that system fluid contains proper glycol
concentration and inhibitor level. The system should
be tested at least once a year and as recommended by
the manufacturer of the glycol solution. Allowance
should be made for expansion of the glycol solution.
Warning
Poison Hazard. Use only inhibited propylene
glycol solutions specifically formulated for
hydronic systems. Do not use ethylene glycol,
which is toxic and can attack gaskets and seals
used in hydronic systems. Use of ethylene
glycol could result in property damage, personal
injury or death.
E. Condensate Overflow Switch and Condensate
Trap Removal and Replacement:
For removal or replacement of the condensate overflow
switch and/or condensate trap follow the steps below. For
parts identification, refer to Section XIII “Repair Parts”.
Xi. Service and Maintenance
(continued)
Figure 61: Condensate Overflow Switch Orientation
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...