135
appendix a - instructions for High altitude installations above 2000 ft.
These instructions apply only to the following Alpine boiler configurations:
2001 ft- 4500 ft, 4501 ft- 6000 ft, 6001
ft- 7800 ft, 7801 ft - 10,000 ft.
These instructions contain specific instructions to properly set up your boiler to ensure proper
operation.
DangEr
These instructions include a procedure for adjusting the air-fuel mixture on this boiler. This procedure
requires a combustion analyzer to measure the CO
2
(or Oxygen) and Carbon Monoxide (CO air free) levels in
flue gas. Adjusting the air-fuel mixture without a proper combustion analyzer could result in unreliable boiler
operation, personal injury, or death due to carbon monoxide poisoning.
Warning
Failure to set up the Boiler in accordance with these instructions could result in high amount of Carbon
Monoxide to be produced which could result in death, serious injury, and/or reduced component life.
Warning
if installing aLP500C or aLP700C: Do not convert aLP500C to LP gas (propane) at altitudes above 6000 ft.
also, do not install aLP700C LP gas (propane) at altitudes above 7800 ft. attempts to do so may result in
unreliable operation, property damage, personal injury or loss of life due to carbon monoxide (CO air free)
poisoning.
Warning
LP Conversions - Alpine boiler setup from factory is configured for use with natural gas installed from
0 - 2000 ft above sea level only. For aLP399C or aLP500C conversion to LP at altitude above 2000 ft,
follow these instructions as specific instructions must be followed when converting for use with LP. If
the information in these instructions is not followed exactly, a fire, an explosion or production of carbon
monoxide may result causing property damage, personal injury or loss of life. The qualified service agency
is responsible for proper installation of this boiler for use with LP gas. The installation is not proper and
complete until the operation of the converted appliance is checked as specified in the manufacturer’s
instructions supplied. aLP600C, aLP700C and aLP800C are factory shipped as either natural gas build or
LP gas build. Field conversions of aLP600C, aLP700C and aLP800C are not permitted.
7. Press 5-digit display to open keypad. Enter
password “086” and press return arrow to close
keypad. Press “Save” button.
8. Press “Adjust” button to enter Adjustment
Mode.
9. Press “Modulation Setup” button.
10. Press “Adjust” button on Boiler Type screen.
11. Use the ↓ ↑ arrows to select the correct size
and altitude of your boiler. Press the
button
to enter your selection. See Figure 56.
12. Press “Enter” button until display stops
blinking. Press “Next” and repeat until
“Completed” is displayed.
13. Press “
” to exit.
Adjusting Boiler Type (must be completed first)
Select the correct Alpine boiler size and altitude
range using the touch screen display as follows:
1. Check boiler’s label for actual boiler size.
2. Confirm installation altitude .
3. Power up the boiler. Display will show the
Home screen.
4. Press “Adjust” button on Home screen.
5. Press “Adjust” button on Adjust Mode screen.
6. Press “Login” button to access Password
screen.
Figure 56: Boiler Model (Boiler Type) Decoding
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...