
102
X. Operation
F. Changing Adjustable Parameters (continued)
“Press”
Domestic
Hot Water
button to access the following parameters:
Factory
Setting
range / Choices
Parameter and Description
170°F
(76.7°C)
50°F to 190°F
(10°C to 87.8°C)
Domestic Hot Water Setpoint
The Domestic Hot Water (DHW) Setpoint parameter is used to create a minimum boiler water
temperature setpoint that is used when DHW heat demand is “on”.
When the DHW heat demand is not “on” (the contact is open or
not wired
) this setpoint is
ignored.
160°F
(71.1°C)
50°F to 190°F
(10°C to 87.8°C)
Domestic Hot Water Thermostat “Sleep” or “away” Setback Setpoint
Thermostat setback setpoint is used when the EnviraCOM thermostat is in “leave” or “sleep”
modes and sensed at E-COM terminals D, R, and C. When setback is “on” the thermostat
setback setpoint shifts the DHW setpoint to lower the DHW temperature and to save energy
while home is in a reduced room temperature mode.
7°F
(-3.9°C)
3°F to 29°F
(-16.1°C to 1.7°C)
Domestic Hot Water Diff above
The boiler stops when the water temperature rises ‘Diff Above’ degrees above the setpoint.
5°F
(-15.0°C)
3°F to 89°F
(-16.1°C to -1.7°C)
Domestic Hot Water Diff Below
The boiler starts when the water temperature drops ‘Diff Below’ degrees below the setpoint.
3
1 to 5
response Speed
This parameter adjusts the Domestic Hot Water temperature controller Proportion Integral
Derivative (PID) values. Higher values cause a larger firing rate change for each degree of
temperature change. If set too high firing rate “overshoots” required value, increases to high fire
causing the temperature to exceed the “Diff Above” setpoint and cycle the boiler unnecessarily.
Lower values cause a smaller firing rate change for each degree of temperature change. If set
too low, the firing rate response will be sluggish and temperature will wander away from setpoint.
10
seconds 0 to 1800 seconds
Low Fire Hold Time
“Low Fire Hold Time” is the number of seconds the control will wait at low fire modulation rate
before being released to modulate. After ignition and flame stabilization periods the firing rate is
held at low fire for “Low Fire Hold Time”. This delay allows heat to travel out to the indirect water
heater and provide feedback prior to the control modulating firing rate.
Enabled
Enable, Disable
Domestic Hot Water Priority (DHWP)
When Domestic Hot Water Priority is Enabled and Domestic Hot Water (DHW) heat demand is
“on” the DHW demand will take “Priority” over home heating demand. When the System and
Boiler pumps are configured as “Central Heat (off DHW priority)” or “Central Heat, Optional
Priority” then they will be forced “off” during DHW Priority. Priority protection time is provided to
end DHWP in the event of a failed or excessive long DHW demand.
60 min.
0 to 90 min.
Priority Time
When DHWP is Enabled the Priority Time Parameter appears and is adjustable.
DHW
Terminal
DHW Terminal,
Zone Control
Domestic Demand Source
Domestic Hot Water demand may respond to the boiler’s DHW Demand terminals or the Sage
Zone Control Panel (if used).
DHW Terminal: Boiler responds to DHW Demand terminals on boiler low voltage PCB.
Zone Control: Boiler responds to Sage Zone Control Panel.
Outlet
Sensor
Outlet Sensor,
DHW Sensor
DHW Modulation Sensor
Outlet Sensor: Boiler modulates for DHW Demand in response to supply/outlet sensor in
boiler.
DHW Sensor: Boiler modulates for DHW Demand in response to DHW sensor at inlet to
indirect water heater. Use for single boiler servicing indirect water heater.
Summary of Contents for Alpine ALP500C
Page 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Page 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Page 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Page 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Page 124: ...124 XIII Repair Parts continued ...
Page 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Page 130: ...130 XIII Repair Parts continued ...
Page 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Page 143: ...143 ...
Page 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...