E6581158
F-6
6
[
H
=
(Reverse)]: If an F command and an R command are entered simultaneously,
the motor will run in the reverse direction.
Output frequency [Hz]
Forward run
Reverse run
Run forward signal
Run backward signal
ON
OFF
ON
OFF
0
Set frequency
Set frequency
Time [s]
6.2.2 Changing the functions of VIA and VIB terminals
H
: VIA/VIB terminal function selection
•
Function
This parameter allows you to choose between signal input and contact signal input for the VIA and VIB
terminals.
Q
Parameter setting
Title
Function
Adjustment range
Default setting
H
Analog/contact input
function selection
(VIA/VIB terminal)
0: VIA - analog input VIB
-
anolog input
1: VIA - anolog input VIB
-
contact input (Sink)
2: VIA - analog input VIB
-
contact input (Source)
3: VIA
-
contact input (Sink) VIB
-
contact input
(Sink)
4: VIA
-
contact input (Source) VIB
-
contact input
(Source)
0
*
When using the VIA and VIB terminals as contact input terminals in sink logic connection, be sure to
insert a resistor between the P24 terminal and the VIA/VIB terminals. (Recommended resistance: 4.7k
Ω
-
1/2W)
Note: When using the VIA terminal as a contact input terminal, be sure to turn the VIA slide switch to the V
position.