Table of output terminal functions 2
Function
No.
Code
Function
Action
12
OT
Over-torque detection
ON: Torque current is equal to or larger than
H
set value and longer than
H
set time.
OFF: The torque current is equal to or less than
(
H
set value -
H
set value).
13
OTN
Inversion of over-torque detection
Inversion of OT
14
RUN
Start/Stop
ON: When operation frequency is output or during
(
FD
)
OFF: Operation stopped
15
RUNN
Inversion of RUN/STOP
Inversion of RUN setting
16
POL
OL pre-alarm
ON: 50% or more of calculated value of overload
protection level
OFF: Less than 50% of calculated value of
overload protection level
17
POLN
Inversion of OL pre-alarm
Inversion of POL setting
18
POHR
Braking resistor overload pre-alarm
ON: 50% or more of calculated value of
H
set overload protection level
OFF: Less than 50% of calculated value of
H
set overload protection level
19
POHRN
Inversion of braking resistor overload pre-alarm
Inversion of RCHR setting
20
POT
Over-torque detection pre-alarm
ON: Torque current is equal to or larger than 70%
of
H
set value.
OFF: The torque current is below (
H
set
value x 70% -
H
set value).
21
POTN
Inversion of over-torque detection pre-alarm
Inversion of POT setting
22
PAL
Pre-alarm
One of the following is turned on:
ON POL, POHR, POT, MOFF, UC, OT, LL
stop, CCT, and momentary power failure
slowdown stop.
or
E
,
R
,
QTJ
issues an alarm
All the following are turned off:
OFF POL, POHR, POT, MOFF, UC, OT, LL
stop, CCT, and momentary power failure
slowdown stop.
or
E
,
R
,
QTJ
issues no alarm
23
PALN
Inversion of pre-alarm
Inversion of PAL setting
24
UC
Small-current detection
ON: The output current is equal to or less than
H
set value for
H
set time.
OFF: The output current is equal to or larger than
H
set value + 10%.
25
UCN
Inversion of small-current detection
Inversion of UC setting
26
HFL
Significant failure
ON:
QEC
,
QEN
,
QV
,
G
,
GGR
,
GVP
,
GRJQ
,
GTT
-
,
QJ
,
WR
,
GH
,
WE
,
GV[R
,
QTGRJ
)
OFF: Failure other than the above
27
HFLN
Inversion of significant failure
Inversion of HFL setting
28
LFL
Insignificant failure
ON: (
QE
-
,
QR
-
,
QJ
,
QN
-
,
QNT
)
OFF: Failure other than the above
29
LFLN
Inversion of insignificant failure
Inversion of LFL setting
30
RDY1
Ready for operation (including ST/RUN)
ON: Ready for operation (ST and RUN are also
ON)
OFF: Others
31
RDY1N
Inversion of ready for operation (including
ST/RUN)
Inversion of RDY1 setting
32
RDY2
Ready for operation (excluding ST/RUN)
ON: Ready for operation (ST and RUN are not
ON)
OFF: Others
33
RDY2N
Inversion of ready for operation (excluding ST/RUN)
Inversion of RDY2
34
FCVIB
Frequency VIB selection
ON: VIB selected as frequency command
OFF: Terminal other than VIB selected as
frequency command