Specifying an operation mode, using parameters
C
C
C
CW
W
W
W
: Automatic function setting
•
Function
Automatically programs all parameters (parameters described below) related to the functions by selecting
the inverter's operating method.
The major functions can be programmed simply.
[Parameter setting]
Title
Function
Adjustment range
Default setting
CW
Automatic function setting
0: Disabled
1: Coast stop
2: 3-wire operation
3: External input UP/DOWN setting
4: 4-20mA current input operation
0:
Automatically programmed functions and parameter set values
Default setting
1: Coast stop
2: 3-wire opera-
tion
3: External input
UP/DOWN set-
ting
4: 4-20mA
current input
operation
EOF
1: Operation
panel
0: Terminal board
0: Terminal board
0: Terminal board
0: Terminal board
HOF
0: Potentiometer
0: Potentiometer
0: Potentiometer
5: UP/DOWN
from external
contact
1: VIA
H
(Always)
1: ST
0: Disabled
1: ST
1: ST
1: ST
H
(F)
2:F
2:F
2:F
2:F
2:F
H
(R)
3:R
3:
3:R
3:R
3:R
H
(RES)
10: RES
10: RES
10: RES
10: RES
10: RES
H
(S1)
6: SS1
6: SS1
6: SS1
41:UP
6: SS1
H
(S2)
7: SS2
7: SS2
7: SS2
42: DOWN
7: SS2
H
(S3)
8: SS3
1: ST
49: HD
43: CLR
38: FCHG
H
0 (%)
-
-
-
20 (%)
Note) See K-15 for input terminal functions.
Disabled (
CW
=
)
Input terminals and parameters are standards programmed at the factory.
Coast stop (
CW
=
)
Setting for coast stopping. In sink logic mode, closing the circuit between the S3 and CC terminals places
the inverter in standby mode and opening the circuit places it in coast stop mode, because ST (standby sig-
nal) is assigned to the S3 terminal.