E6581158
F-2
6
An example of the connection of the open collector OUT terminal
An example of the connection of the relay output terminals
•
Output terminal setting
Output of the low-speed signal (ON signal) between the RY and RC terminals is the factory default
setting of the output terminal selection parameter. This setting must be changed to invert the polarity of
the signal.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Output terminal selection 1A (RY-RC)
0-255
(See Section 11, K-18)
4 (ON signal)
or
5 (OFF signal)
Set
H
to output to OUT-NO terminals.