E6581158
K-16
11
Q
Table of input terminal functions 2
Function
No.
Code
Function
Action
34
F+SS3+AD2
Combination of forward run, preset-speed
command 3 and acceleration/deceleration 2
ON: Simultaneous input from F, SS3 and AD2
35
R+SS3+AD2
Combination of reverse run, preset-speed
command 3 and acceleration/deceleration 2
ON: Simultaneous input from R, SS3 and AD2
36
F+SS4+AD2
Combination of forward run, preset-speed
command 4 and acceleration/deceleration 2
ON: Simultaneous input from F, SS4 and AD2
37
R+SS4+AD2
Combination of reverse run, preset-speed
command 4 and acceleration/deceleration 2
ON: Simultaneous input from R, SS4 and AD2
38
FCHG
Frequency command forced switching
ON:
H
ҏ
(If
H
=
)
OFF:
HOQF
39
VF2
No.2 Switching of V/F setting
ON: No.2 V/F setting
(
RV
=0,
H
,
H
,
H
,
H
)
OFF: No.1 V/F setting
(Set value of
RV
,
XN
,
XNX
,
XD
,
VJT
)
40
MOT2
No.2 motor switching
(
VF2
+
AD2
+
OCS2
)
ON: No.2 motor
(
RV
=0,
H
,
H
,
H
,
H
,
H
,
H
,
H
,
H
)
OFF: No.1 motor (Set value of
RV
,
XN
,
XNX
,
XD
,
VJT
,
CEE
,
FGE
,
H
,
H
)
41
UP
Frequency UP signal input from external contacts
ON: Increase in frequency
42
DOWN
Frequency DOWN signal input from external
contacts
ON: Reduction in frequency
43
CLR
Frequency UP/DOWN cancellation signal input
from external contacts
OFF
→
ON: Resetting of UP/DOWN frequency by
means of external contacts
44
CLR+RES
Combination of frequency UP/DOWN cancellation
and reset by means of external contacts
ON: Simultaneous input from CLR and RES
45
EXTN
Inversion of trip stop command from external
device
OFF:
G
Trip stop
46
OH
Thermal trip stop signal input from external device
ON:
QJ
Trip stop
47
OHN
Inversion of thermal trip stop command from
external device
OFF:
QJ
Trip stop
48
SC/LC
Forced switching from remote to local control
Enabled when remote control is exercised
ON: Local control (setting of
HOQF
and
H
)
OFF: Remote control
49
HD
Operation holding (stop of 3-wire operation)
ON: F (forward run)/R: (reverse run) held, 3-wire
operation
OFF: Slowdown stop
50
CMTP
Forced switching of command mode and terminal
board command
ON: Terminal board operation
OFF: Setting of
EOQF
51
CKWH
Display cancellation of the cumulative power
amount (kWh)
ON: Monitor display cancellation of the cumulative
power amount (kWh)
52
FORCE
Forced operation (factory configuration required)
ON: Forced operation mode in which operation is
not stopped in the event of the occurrence of
a soft fault (preset speed operation frequency
15) To use this function, the inverter needs to
be so configured at the factory.
OFF: Normal operation
53
FIRE
Fire-speed control
ON: Fire-speed operation (preset speed operation
frequency 15)
OFF: Normal operation