– 38 –
Ts + 1
Ts – 1
Ta
Cooling operation
Monitoring (Fan)
Heating operation (Heat pump model)
Fan only operation (Cooling-only model)
Tsc
+0.5
+1.0
[˚C]
Ta
Fan speed
L– (W5)
(W5+W3) / 2
SL (W3)
Item
1. Basic
operation
(Continued)
Operation flow and applicable data, etc.
4. AUTO operation
Selection of operation mode
As shown in the following figure, the operation starts by
selecting automatically the status of room temperature
(Ta) when starting AUTO operation.
∗
1. When reselecting the operation mode, the fan speed is
controlled by the previous operation mode.
5. DRY operation
DRY operation is performed according to the difference
between room temperature and the setup temperature
as shown below.
In DRY operation, fan speed is controlled in order to
prevent lowering of the room temperature and to avoid
air flow from blowing directly to persons.
Description
1) Detects the room temperature (Ta)
when the operation started.
2) Selects an operation mode from Ta in
the left figure.
3) Fan operation continues until an
operation mode is selected.
4) When AUTO operation has started
within 2 hours after heating operation
stopped and if the room temperature is
20°C or more, the fan operation is
performed with ”Super Ultra LOW”
mode for 3 minutes.
Then, select an operation mode.
5) If the status of compressor-OFF
continues for 15 minutes the room
temperature after selecting an
operation mode (COOL/HEAT),
reselect an operation mode.
1) Detects the room temperature (Ta)
when the DRY operation started.
2) Starts operation under conditions in
the left figure according to the
temperature difference between the
room temperature and the setup
temperature (Tsc).
Setup temperature (Tsc)
= Set temperature on remote controller
(Ts) + (0.0 to 1.0)
3) When the room temperature is lower
1°C or less than the setup
temperature, turn off the compressor.