– 29 –
RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E
RAS-M18GACV-E
NOTE :
• The maximum pipe length of this air conditioner is 30 m. When the pipe length exceeds 20 m, the additional
charging of refrigerant, 20 g per 1m for the part of pipe exceeded 20 m is required. (Max. 200g)
Per 1 unit
Max. : 20m
Min. : 2m
Total : 30m
Chargeless =20m
Charge
=20g/m
(21 to 30m)
Deoxidized copper pipe
Both A and B rooms
Outer dia. : 9.52mm (10,13)
:12.7mm (16)
Thickness : 0.8mm
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Indoor fan
Deoxidized copper pipe
Both A and B room
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allo
w
a
b
le height
diff
erence :
10m
Allo
w
a
b
le pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse motor
valve at liquid side
(CAM-B22YGTF-3)
TD
TGa
TGb
4-way valve
(STF-0108Z)
Compressor
DA111A1F-20F1
TS
T2
Outdoor heat
exchanger
Temp. measurement
Propeller fan
Refrigerant amount : 1.20kg
OUTDOOR UNIT
To B room
Muffler
TE
Ta
Ø2.2 x 200
Split capillary
Ø2.2 x 200
Split capillary
To B room
Tca
*1