– 101 –
Air ionizer
Connector
Drain guide
Press the
claw here
Press the
claw here
Pull here
Screw
Claw
Claw
Claw
Check whether the
leads have been
completely inserted.
Claw
Claw
Claw
Check whether the
leads have been
completely inserted.
No.
2
Part name
High voltage
generator
Procedures
1) Follow to the procedure in the item
1
.
2) Remove the drain guide.
3) To remove the air ionizer from the back body,
pull it toward you while pressing down on its
left and right claws.
Disconnect the two leads (black) connected to
the air ionizer from where they are fitted into
the other components.
(Caution: do not remove the Faston.)
4) Disconnect the connectors of the high-voltage
generator, and disconnect the four leads from
where they are fitted into the other components.
5) Remove the fixing screw which secures the
high voltage generator, and remove the high
voltage generator from the evaporator.
<How to assemble the high voltage generator>
1) Insert the high voltage generator straight into
the evaporator, and secure it using the fixing
screw.
2) Pass the leads of the high voltage generator
through the area designated and insert them
into its connectors.
3) Attach the air ionizer to the back body, and
pass the two leads (black) through the area
designated on the electric parts box assembly.
4) Attach the drain guide.
Remarks