– 82 –
Check
code
Check
code
Block distinction
Operation of diagnosis function
Block
Outdoor
P.C. board
Not
displayed
Outdoor
P.C. board
Others
(including
compressor)
Cause of operation
Inverter over-current
protective circuit
operates. (Short time)
Position-detect circuit
error or short-circuit
between windings of
compressor
Current-detect circuit
error
Being out of place,
disconnection or short-
circuit of the outdoor
temp. sensor (Ts)
Disconnection or short-
circuit of discharge
temp. sensor
Outdoor fan drive
system error
Outdoor temp. sensor
error
Compressor drive
output error,
Compressor error
(lock, missing, etc.),
Break down
Return serial signal has
been sent when
operation started, but it
is not sent from halfway.
1) Compressor thermo.
operation Gas
shortage Gas leak
2) Instantaneous power
failure
Compressor does not
rotate. (Current
protective circuit does
not operate when a
specified time passed
after compressor had
been activated.)
Discharge temp.
exceeded 117°C
Break down of
compressor
Air
conditioner
status
All off
All off
All off
All off
All off
All off
Operation
continues
All off
Operation
continues
All off
All off
All off
Remarks
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
——
Displayed when
error is detected.
Flashes when
trouble is detected
on return serial
signal, and normal
status when signal
is reset.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Judgment and action
Even if trying operation again,
all operations stop immediately. :
Replace P.C. board.
1. Even if connecting lead wire of
compressor is removed,
position-detect circuit error
occurred. : Replace P.C. board.
2. Measure resistance between
wires of compressor, and
perform short-circuit. :
Replace compressor.
Even if trying operation again, all
operations stop immediately. :
Replace P.C. board.
Check 5-serial LED.
1. Check sensors (TE, TS).
2. Check P.C. board.
1. Check discharge temp. sensor
(TD).
2. Check P.C. board
Position-detect error, over-current
protective operation of outdoor fan
drive system, fan lock, etc. :
Replace P.C. board or fan motor.
1. Check outdoor temp. sensor
(TO).
2. Check P.C. board.
Check 5-serial LED.
When 20 seconds passed after
start-up, position-detect circuit error
occurred. : Replace compressor.
Trouble on P.M.V.
1. Repeat Start and Stop with
interval of approx. 10 to 40
minutes. (Code is not displayed
during operation.)
Supply gas.
(Check also gas leak).
2. Unit operates normally during
check.
If return serial signal does not
stop between indoor terminal
block 2 and 3, replace inverter
P.C. board.
If signal stops between indoor
terminal block 2 and 3, replace
indoor P.C. board.
1. Trouble on compressor
2. Trouble on wiring of compressor
(Missed phase)
1. Check dischage temp. sensor
(TD).
2. Gas leakage
3. Trouble on P.M.V.
1. Check power voltage.
(220–230–240 V +10%)
2. Overload operation of
refrigeration cycle
Check installation condition
(Short-circuit of outdoor diffuser).