6 F 2 T 0 1 7 2
PHAR class
Attribute Name
Attr. Type
Explanation
T
M/O
GRE110
LNName
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node
Class
M
OpCntRs
INC
Resetable operation counter
O
N
Status Information
Str
ACD
Start
M
Y
Settings
HarRst
ING
Number of harmonic restrained
O
N
PhStr
ASG
Start Value
O
Y
PhStop
ASG
Stop Value
O
N
OpDlTmms
ING
Operate Delay Time
O
N
RsDlTmms
ING
Reset Delay Time
O
N
PTOC class
Attribute Name
Attr. Type
Explanation
T
M/O
GRE110
LNName
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node
Class
M
OpCntRs
INC
Resetable operation counter
O
N
Status Information
Str
ACD
Start
M
Y
Op
ACT
Operate
T
M
Y
TmASt
CSD
Active curve characteristic
O
N
Settings
TmACrv
CURVE
Operating Curve Type
O
N
StrVal
ASG
Start Value
O
Y
TmMult
ASG
Time Dial Multiplier
O
N
MinOpTmms
ING
Minimum Operate Time
O
N
MaxOpTmms
ING
Maximum Operate Time
O
N
OpDITmms
ING
Operate Delay Time
O
Y
TypRsCrv
ING
Type of Reset Curve
O
N
RsDITmms
ING
Reset Delay Time
O
N
DirMod
ING
Directional Mode
O
N
PTRC class
Attribute Name
Attr. Type
Explanation
T
M/O
GRE110
LNName
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node
Class
M
OpCntRs
INC
Resetable operation counter
O
N
Status Information
Tr
ACT
Trip
C
Y
Op
ACT
Operate (combination of subscribed Op from protection functions)
C
N
Str
ACD
Sum of all starts of all connected Logical Nodes
O
N
Settings
TrMod
ING
Trip Mode
O
N
TrPlsTmms
ING
Trip Pulse Time
O
N
Condition C: At least one of the two status information (Tr, Op) shall be used.
310
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...