6 F 2 T 0 1 7 2
Menu
Name
Range
Contents
Default
Protection
SEF
SE2R
DEF / DEP
SEF2 Reset
Characteristic.
(if MSE2=IEEE,US or C)
-- (DEF)
SE2-2F
NA / Block
SEF2 2f Block Enable
-- (NA)
SE3EN
Off / On
SEF3 Enable
-- (Off)
SE3-2F
NA / Block
SEF3 2f Block Enable
-- (NA)
SE3-DIR
FWD / REV / NON
SEF1 Directtional
-- (NON)
SE4EN
Off / On
SEF4 Enable
-- (Off)
SE4-2F
NA / Block
SEF4 2f Block Enable
-- (NA)
SE4-DIR
FWD / REV / NON
SEF1 Directtional
-- (NON)
ZPEN
Off / On
Residual Power block
Enable
-- (Off)
THM
THMEN
Off / On
Thermal Overload
Enable
Off
THMAEN
Off / On
Thermal Alarm Enable
Off
NPS
NPS1EN
Off / On
NPS1 Enable
Off
NPS1-2F
NA / Block
NPS1 2f Block Enable
NA
NPS2EN
Off / On
NPS2 Enable
Off
NPS2-2F
NA / Block
NPS2 2f Block Enable
NA
BCD
BCDEN
Off / On
Broken conductor
Enable
Off
BCD-2F
NA / Block
BCD 2f Block Enable
NA
CBF
BTC
Off / On
Back-Trip Control
Off
RTC
Off / DIR / OC
Re-trip Control
Off
CLP
CLSG
Off / 1 /2
Cold Load
settings group
Off
CLDOEN
Off / On
Cold Load
drop-off Enable
Off
ARC
ARCEN
Off / On
Autoreclosing Enable.
Off
ARC-NUM
S1 / S2 / S3 / S4 /
S5
Reclosing shot max.
number
S1
OC1-INIT
NA / On / Block
Autoreclosing initiation by
OC1 enable
NA
OC1-TP1
Off -/Inst / Set
OC1 trip mode of 1st trip
Set
OC1-TP2
Off -/Inst / Set
OC1 trip mode of 2nd trip
Set
OC1-TP3
Off -/Inst / Set
OC1 trip mode of 3rd trip
Set
OC1-TP4
Off -/Inst / Set
OC1 trip mode of 4th trip
Set
OC1-TP5
Off -/Inst / Set
OC1 trip mode of 5th trip
Set
OC1-TP6
Off -/Inst / Set
OC1 trip mode of 6th trip
Set
OC2-INIT
NA / On / Block
Autoreclosing initiation by
OC2 enable
NA
OC2-TP1
Off -/Inst / Set
OC2 trip mode of 1st trip
Set
OC2-TP2
Off -/Inst / Set
OC2 trip mode of 2nd trip
Set
OC2-TP3
Off -/Inst / Set
OC2 trip mode of 3rd trip
Set
OC2-TP4
Off -/Inst / Set
OC2 trip mode of 4th trip
Set
OC2-TP5
Off -/Inst / Set
OC2 trip mode of 5th trip
Set
OC2-TP6
Off -/Inst / Set
OC2 trip mode of 6th trip
Set
OC3-INIT
NA / On / Block
Autoreclosing initiation by
OC3 enable
NA
OC3-TP1
Off -/Inst / Set
OC3 trip mode of 1st trip
Set
OC3-TP2
Off -/Inst / Set
OC3 trip mode of 2nd trip
Set
OC3-TP3
Off -/Inst / Set
OC3 trip mode of 3rd trip
Set
235
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...