6 F 2 T 0 1 7 2
O f F / O n
S E 4 - D I R 0
Display at model 820 series.
F W D / R E V / N O N
S E 4 - 2 F 0
N A / B l o c k
Z P E N 0
Display at model 820 series.
O f f / O n
<
SE1EN
>
, <SE2EN>
•
Enter 1(=On) to enable the SEF1 or SEF2 and press the ENTER key. If disabling the SEF1,
enter 0(=Off) and press the ENTER key.
<
SE
∗
-DIR
>
The settings are for model 820 series,to set SEF
∗
directional characteristic, do the following.
•
Enter 0(=FWD) or 1(=REV) or 2(=NON) and press the
ENTER
key.
<
MSE1C
>
, <MSE2C>
To set the Inverse Curve Type, do the following.
•
If [MSE1] or [MSE2] is 1(=IEC), enter 0(=NI) or 1(=VI) or 2(=EI) or 3(=LTI) and press the
ENTER key.
•
If [MSE1] or [MSE2] is 2(=IEEE), enter 0(=MI) or 1(=VI) or 2(=EI) and press the ENTER
key.
•
If [MSE1] or [MSE2] is 3(=US), enter 0(=CO2) or 1(=CO8) and press the ENTER key.
<
SE1R
>
, <SE2R>
To set the Reset Characteristic, do the following.
•
If [MSE1] or [MSE2] is 2(=IEEE) or 3(=US), enter 0(=DEF) or 1(=DEP) and press the
ENTER key.
<
SE1S2
>
To set the Stage 2 Timer Enable, do the following.
•
Enter 1(=On) to enable the SE1S2 and press the ENTER key. If disabling the SE1S2, enter
0(=Off) and press the ENTER key.
<
SE3EN, SE4EN
>
•
Enter 1(=On) to enable the SEF3 and press the ENTER key. If disabling the SEF3, enter
0(=Off) and press the ENTER key. The SEF4 is the same.
<
SE1-2F, SE2-2F, SE3-2F, SE4-2F
>
•
Enter 1(=Block) to block the SE1, SE2, SE3 and SE4 against the inrush current, and press the
ENTER
key.
123
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...