6 F 2 T 0 1 7 2
INF
Description
Contents
GI
Typ
e ID
COT
FUN
Fault Indications
64
Start/pick-up L1
A phase, A-B phase or C-A phase element pick-up
GI
2
1, 7, 9
160
65
Start/pick-up L2
B phase, A-B phase or B-C phase element pick-up
GI
2
1, 7, 9
160
66
Start/pick-up L3
C phase, B-C phase or C-A phase element pick-up
GI
2
1, 7, 9
160
67
Start/pick-up N
Earth fault element pick-up
GI
2
1, 7, 9
160
68
General trip
BO status specified by IECGT: ON (*1)
--
2
1, 7
160
69
Trip L1
BO status specified by IECAT: ON (*1)
--
2
1, 7
160
70
Trip L2
BO status specified by IECBT: ON (*1)
--
2
1, 7
160
71
Trip L3
BO status specified by IECCT: ON (*1)
--
2
1, 7
160
72
Trip I>>(back-up)
Back up trip
Not supported
73
Fault location X In ohms
Fault location (prim. [ohm] / second. [ohm] / km selectable by
IECFL)
Not supported
74
Fault forward/line
Forward fault
Not supported
75
Fault reverse/Busbar
Reverse fault
Not supported
76
Teleprotection Signal
transmitted
Carrier signal sending
Not supported
77
Teleprotection Signal received
Carrier signal receiving
Not supported
78
Zone1
Zone 1 trip
Not supported
79
Zone2
Zone 2 trip
Not supported
80
Zone3
Zone 3 trip
Not supported
81
Zone4
Zone 4 trip
Not supported
82
Zone5
Zone 5 trip
Not supported
83
Zone6
Zone 6 trip
Not supported
84
General Start/Pick-up
Any elements pick-up
GI
2
1, 7, 9
160
85
Breaker Failure
CBF trip or CBF retrip
--
2
1, 7
160
86
Trip measuring system L1
Not supported
87
Trip measuring system L2
Not supported
88
Trip measuring system L3
Not supported
89
Trip measuring system E
Not supported
90
Trip I>
Inverse time OC trip (OC1 trip)
--
2
1, 7
160
91
Trip I>>
Definite time OC trip (OR logic of OC1 to OC3 trip)
--
2
1, 7
160
92
Trip IN>
Inverse time earth fault OC trip (OR logic of EF1 and SEF1 trip)
--
2
1, 7
160
93
Trip IN>>
Definite time earth fault OC trip (OR logic of EF1 to EF3 and
SEF1 to SEF3 trip)
--
2
1, 7
160
Autoreclose indications
128
CB 'ON' by Autoreclose
CB close command output
--
1
1, 7
160
129
CB 'ON' by long-time
Autoreclose
Not supported
130
Autoreclose Blocked
Autoreclose block
GI
1
1, 7, 9
160
Note (*1): Not available if the setting is "0".
(
∗
2): Not available when neither the EF nor SEF element is used.
293
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...