6 F 2 T 0 1 7 2
Menu
Name
Range
Contents
Default
EF
0.10 – 100.00 A
EF element
for disturbance
0.60
SEF
0.025 – 2.500 A
SEF element
for disturbance
--(0.200)
NPS
0.10 – 10.00 A
NPS element
for disturbance
0.40
Trip
Off / On
Disturbance trigger
On
BI
Off / On
Disturbance trigger
On
OC
Off / On
Disturbance trigger
On
Disturbance
Record
EF
Off / On
Disturbance Trigger
On
SEF
Off / On
Disturbance Trigger
--(Off)
NPS
Off / On
Disturbance Trigger
On
SIG1
0 - 312
Disturbance Trigger
51
SIG2
0 - 312
52
SIG3
0 - 312
53
SIG4
0 - 312
63
SIG5
0 - 312
102
SIG6
0 - 312
103
SIG7
0 - 312
104
SIG8
0 - 312
117
SIG9
0 - 312
141
SIG10
0 - 312
142
SIG11
0 - 312
143
SIG12
0 - 312
144
SIG13
0 - 312
145
SIG14
0 - 312
0
SIG15
0 - 312
0
SIG16
…
30
0 - 312
0
SIG31
0 - 312
0
SIG32
0 - 312
0
Counter
TCSPEN
Off / On / Opt-On
Trip Circuit
Supervision Enable
Off
CBSMEN
Off / On
Circuit Breaker
State Monitoring
Alarm Enable
Off
TCAEN
Off / On
Trip Count Alarm
Enable
Off
Σ
IyALM
Off / On
Σ
Iy Alarm Enable
Off
OPTAEN
Off / On
Operate Time
Alarm Enable
Off
TCALM
1 – 10000
Trip Count Alarm
Threshold
10000
Σ
IyALM
10 – 10000 E6
Σ
Iy Alarm
Threshold
10000
YVALUE
1.0 – 2.0
Y value
2.0
OPTALM
100 – 5000 ms
Operate Time
Alarm Threshold
1000
Status
Display
Pri / Sec / Pri-A
Metering
Pri
Time sync.
Off / BI / Modbus /
103 / SNTP
Time
Off
228
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...