6 F 2 T 0 1 7 2
Application association
S2
Associate
M
M
Y
S3
Abort
M
M
Y
S4
Release
M
M
Y
Logical device
S5
GetLogicalDeviceDirectory
M
M
Y
Logical node
S6
GetLogicalNodeDirectory
M
M
Y
S7
GetAllDataValues
O
M
Y
Data
S8
GetDataValues
M
M
Y
S9
SetDataValues
O
O
N
S10
GetDataDirectory
O
M
Y
S11
GetDataDefinition
O
M
Y
Data set
S12
GetDataSetValues
O
M
Y
S13
SetDataSetValues
O
O
N
S14
CreateDataSet
O
O
N
S15
DeleteDataSet
O
O
N
S16
GetDataSetDirectory
O
O
Y
Substitution
S17
SetDataValues
M
M
N
Setting group control
S18
SelectActiveSG
O
O
Y
S19
SelectEditSG
O
O
N
S20
SetSGValues
O
O
N
S21
ConfirmEditSGValues
O
O
N
S22
GetSGValues
O
O
N
S23
GetSGCBValues
O
O
Y
Reporting
Buffered report control block (BRCB)
S24
Report
c6
c6
Y
S24-1
data-change (dchg)
Y
S24-2
quality-change (qchg)
Y
S24-3
data-update (dupd)
N
S25
GetBRCBValues
c6
c6
Y
S26
SetBRCBValues
c6
c6
Y
Unbuffered report control block (URCB)
S27
Report
c6
c6
Y
S27-1
data-change (dchg)
Y
S27-2
quality-change (qchg)
Y
S27-3
data-update (dupd)
N
S28
GetURCBValues
c6
c6
Y
S29
SetURCBValues
c6
c6
Y
Logging
Log control block
S30
GetLCBValues
M
M
N
S31
SetLCBValues
O
M
N
Log
S32
QueryLogByTime
c7
M
N
S33
QueryLogAfter
c7
M
N
S34
GetLogStatusValues
M
M
N
Generic substation event model (GSE)
GOOSE-CONTROL-BLOCK
S35
SendGOOSEMessage
c8
c8
Y
S36
GetGoReference
O
c9
N
S37
GetGOOSEElementNumber
O
c9
N
S38
GetGoCBValues
O
O
Y
S39
SetGoCBValues
O
O
Y
GSSE-CONTROL-BLOCK
S40
SendGSSEMessage
c8
c8
N
S41
GetGsReference
O
c9
N
S42
GetGSSEDataOffset
O
c9
N
S43
GetGsCBValues
O
O
N
S44
SetGsCBValues
O
O
N
329
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...