6 F 2 T 0 1 7 2
(2) Modbus address map group
Modbus data model
Address(ID) Number Data specification
Coils
0x0200
1 Remote control (enable flag)
(Read/Write)
0x0400
5
Remote control (command, interlock), Time
synchronization, Clear command (write only)
Discrete Input
0x1000
6 BI
0x1016
5 Relay fail output, BO
(Read Only)
0x1040
14 LED(Relay status, R/L, CB on/off status)
0x1080
16 Virtual LED
0x1201
-
Signal list (see Appendix B for detail)
Input Registers
0x2000
24
Analog data (Ia, Ib, Ic, Ie, Thermal, Ia max etc.,
unconverted to engineering units)
2-word long
(Read Only)
Holding Registers
0x3000
29
Fault record (No., Time, Phase, Type), max. 4 records,
write protected
(Read/Write)
0x3200
72
Event record (No., Time, ID, Status), 10 out of max. 200
records, write protected
0x3800
4 Current time data (IEC format)
0x3810
36
Counter data (number of trips, ∑I
y
, etc), 2-word long
0x3E82
2 Password for remote control
0x4000
-
Setting value (see Appendix H for detail)
0x8000
Undefined after this address
Discrete Inputs
Single bit
Read-Only
Coils
Single bit
Read-Write
Input Registers
16-bit word
Read-Only
Holding Registers
16-bit word
Read-Write
(3)Modbus address map
Address
Description
Supplementary explanation
Coils
Remote control (R/W)
0200
Remote control enable flag
0400
Remote control command
Write (control) is enabled only 0x0200=1 (on/off)
0401
Remote interlock command
Write (control) is enabled only 0x0200=1 (on/off)
0402
Remote reset command
Write (control) is enabled only 0x0200=1 (on)
0403
Time synchronization
command
Call time synchronization task (on)
263
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...