Installation
EF200F-C
28
6.2.4
Mounting the pressure measuring unit
Preparation
1. Prior to mounting the pressure measuring unit, install the measuring device in the
pipe.
2. When mounting the pressure measuring unit, use only the seal provided. The use of a
different sealing material is not permitted.
Removing the blind flange
A0034355
1
Mounting screws
2
blind flange
3
Seal
4
Flange connection on sensor side
When replacing the seal following commissioning, fluid may escape when the flange
connection is opened!
Ensure that the measuring device is not under pressure.
Ensure that there is no fluid in the measuring device.
1. Release the mounting screws on the blind flange.
The screws are needed again to mount the pressure measuring unit.
2. Remove the internal seal.
1.
4
2.
1
3
2
4 x
6 mm
►
►