EF200F-C
Commissioning
73
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Gas type
The following conditions are
met:
• In the Select medium
parameter, the Gas option is
selected.
• In the Select gas type
parameter, the Single gas
option is selected.
Select measured gas type.
• Hydrogen H2
• Helium He
• Neon Ne
• Argon Ar
• Krypton Kr
• Xenon Xe
• Nitrogen N2
• Oxygen O2
• Chlorine Cl2
• Ammonia NH3
• Carbon monoxide
CO
• Carbon dioxide
CO2
• Sulfur dioxide SO2
• Hydrogen sulfide
H2S
• Hydrogen chloride
HCl
• Methane CH4
• Ethane C2H6
• Propane C3H8
• Butane C4H10
• Ethylene C2H4
• Vinyl Chloride
C2H3Cl
Methane CH4
Relative humidity
The following conditions are
met:
• In the Select medium
parameter, the Gas option is
selected.
• In the Select gas type
parameter, the Air option is
selected.
Enter humidity content of air
in %.
0 to 100 %
0 %
Steam calculation mode
The Steam option is selected
in the Select medium
parameter parameter.
Select calculation mode of
steam: based on saturated
steam (T-compensated) or
automatic detection (p-/T-
compensated).
• Saturated steam
(T-compensated)
• Automatic (p-/T-
compensated)
Saturated steam (T-
compensated)
Steam quality
The following conditions are
met:
• Order code for "Application
package":
• Option "Wet steam
measurement"
• The Steam option is
selected in the Select
medium parameter
parameter.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Select compensation mode for
steam quality.
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and Wet Steam
Measurement
application package
• Fixed value
• Calculated value
Fixed value